Maximum transformer rating/circuit breakers in parallel configuration - 2nd round

Jpascp

Electrical
Jan 15, 2025
21
For MV voltage level (36 kV) the maximum nominal current for CB are:

2500 A

3150 A (forced ventilation)

Nowadays there are still the same values or bigger values can be found? Where?
 
Replies continue below

Recommended for you

40 years ago I helped install a 6000 Amp, 13kV SF6 breaker in an underground substation.
 
This manufacturer offers power circuit breakers with 5000 Amp continuous current ratings at the 38kV level:

5000 A in busbars.

Feeders is 2500 A maximum.
 
The footnotes on page 5 of the attachment indicate 3150 A is available with forced cooling for Single-busbar and double-busbar switchgear. With, as mentioned, 5000 A reserved for the main switchgear bus only.






The Siemens 3AH3 breakers are available for 4000 continuous current rating @ 36kV (page 42).

 