  1. surineman

    SPI on INTools

    Everyone, I need user manual or anything can help me to start working with SPI on INTools. I've been on Intergraph website, there is nothing and found some links not available in their website anymore. Any help would be highly appreciated. Regards and thanks
  2. surineman

    Deaerator Level Measurement

    The only thing is I am worried about is the bubbling surface of Deaerator may cause problem in Radar measurement. Any experience with same type of service? Thanks in advance. Regards,
  3. surineman

    Deaerator Level Measurement

    Ashereng, I am not quite sure, since operations are insisting on replacement I did not ask more questions. The only thing that I can think of is the tapping points of either high or low (or maybe both) might have blockage or something like that, although there are a lot of bends in tubing too...
  4. surineman

    Deaerator Level Measurement

    Hi there, We have a spray type deaerator in our boiler house. The existing level measurement on this deaerator is Through a DP cell. it has been found that slight pressure fluctuations in the top deaerator scrubber drum(i.e. a jump in steam pressure for only few psig), have had a huge impact on...
  5. surineman

    Converting Level-Trol controller to tranmitter

    Thank you all for responses. I have to clarify my question I believe: I have a 2500 series Pneumatic level-trol controller from Fisher. I want to convert this controller to just a Pneumatic transmitter with output signal usable for generating an alarm through a pressure switch and shutting...
  6. surineman

    2500 series pneumatic controller

    Hi there, I have a 2500 series level-trol pneumatic controller/transmitter from Fisher. I want to convert this controller to just a pneumatic transmitter. Can anybody help me? any link,reference,.. would be highly appreciated. Regards
  7. surineman

    Converting Level-Trol controller to tranmitter

    Hi there, I have a 2500 series level-trol controller from Fisher. I want to convert this controller to just a transmitter. Can anybody help me? any link,reference,.. would be highly appreciated. Regards
  8. surineman

    Displacer connection taps in boiler application

    Everyone, I have a magnetrol pneumatic level transmitter. I do not have any model or other information for it. I just know that is side and bottom connection.( I can not see it because of tracing around it but piping drawing shows that and we assume it is right) It is installed on a 10"...
  9. surineman

    Cable Size

    By splitter box I mean: The outgoing cable after main breaker would go to a set of terminals which all of feeders to branch breakers are tied to those terminals. As oppose to have a real bus bar and feed the branch circuit breaker from bus bar. For 500kcmil I should use 7 conductor per phase...
  10. surineman

    Cable Size

    Hi Everyone, I have a 2000 kVA transformer 27.6 kV/ 600 V The transformer and electrical service cabinet both are going to be outside and located very close by each other. The code asks for breaker and conductor (secondary) not more than 125% of rated current. 1)What would be the most...
  11. surineman

    Low P.F.

    Everyone, the motor is a Flygt mixer model 4670, here are some information they provide on their website: Rated Power:14.9kW 20.0 hp voltage:600 v Speed (r/min):440 Rated Current: 36.0 A No load Current: 28.0 A Locked Rotor Current: 105.0 A Starting kVA: 109.2 EEMAC CODE : F Efficiency...
  12. surineman

    Low P.F.

    Hi there, I have a large amout of mixers in my plant with low P.F. (0.51 @ 100% load ). There are 50 of them each 20 HP (600 V) and 36.0 A FLA. (High current) With this P.F. I probably have to double size of transformer. Or Is there any way around this? what about capacitor banks? I need...
  13. surineman

    H.V. Primary Connection

    Everyone, I have an Existing Four way load break on my incoming 5 kV feeder and I am going to use one way to my new 500 kW transformer. I need an illustrative reference indicating all HV components needed for Cable termination before XT primary. Regards,
  14. surineman

    Breaker size

    Everyone, I have an existing MCC Panel. One of the branches is 400A breaker feeding another MCC in other building Which its main incoming breaker is 500A. Does anybody can see a reason behind that? what If the total current of second MCC is more than 400? Regards,
  15. surineman

    SLA

    Thank you all. If it is so, why they have to mention it? what would be technical interpretation for it. Regards,
  16. surineman

    SLA

    Everyone, In a motor spec what SLA stands for? Regards,
  17. surineman

    Grounding

    Ralph, Thx for reference but it seems the website facing some difficulties. Regards,
  18. surineman

    Grounding

    Can I use the duct bank used for primary cable to transforner for ground wire? should it be above or lower the power cables if possible? Thx
  19. surineman

    Grounding

    I have a grounging study for a new water treatment plant. We have to design the grounding system for this plant. The plant is located on a granite rock outcorp and soil resistance clearly is high. Depend on spacing of probes the resistance changes from 330 to 102.5 ohms. we want to run a 4 odd...
  20. surineman

    Grounding System Audit Report

    Everybody, We are a consulting firm designing water treatment plants. Another company is going to do a Grounding System Audit Report for our new project. In our electrical drawings we did not generate any drawings regarding this matter but we asked for short circuit and coordination study in...