1. Determine Primary Operating Current,POC, (earth fault tripping current.)
2. Select an appropriate earth fault sensing relay, either 1A or 5A.
3. From above info, the CT ratio can be defined
eg. assume 1A relay and assume POC 2A
if relay set for 10% tripping (of 1A) then CT ratio to be 20:1...