Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Pump Automation 1

EEENGRX

Electrical
Sep 11, 2021
89
I have a self primer pump that requires to manually fill up the primer case with prime water to enable it pick up prime and start pumping and avoid damaging the mechanical seal.The pump is used for a sump that i need to automate based on the sump level.i plan to add a foot valve. do you think this will be sufficient to hold prime or it will just reduce the time it takes to prime the pump?what are the various options for shutdown protection or elert to the control room if the pump does not pick up prime for any reason whatsoever? will aan amp monitor at the bucket work? or a solenoid valve on a timer for the priming water which will be activated by the motor starting, per start and close after a set period of time.allauggestions are highly welcome as i want to go with the best possible option as well as less complicated
 
Replies continue below

Recommended for you

Yes , I was able to solve the priming issue and it’s now working fine.. self priming
Great but you still haven't told us how you solved it. We've put time and either into this post and would like to know how it finally got solved. Please.

I,e, what you have done differently or what have you changed?
 
That foot valve is a necessity in this case, but in the long run, it will turn out to be the weak link in this priming setup. If it is stuck / jammed in some intermediate position, the suction line will not prime. Foot valves fail to work as intended due to corrosion and or bio fouling.
 
Some common pumps use a flooded case and a venturi.
The impeller drives case fluid through the impeller back into the case.
As the impeller draws in fluid, the pressure builds in the case and fluid is forced out the discharge,
These pumps will handle much more entrained air than a straight centrifugal pump, but too much air will eventually cause loss of prime.
The air separates in the case and the discharge is at the top of the case so that the air is purged.
Not speculation.
I lived with a situation where I used one of these pumps as a booster for a very poor domestic supply.
At times the mains would run dry and the pump would lose prime.
I had a 5 gallon bucket, a flexible line and a petcock to re-prime the pump several times a week.
Was it kludgy?
Yes, but it was cheaper than the alternative.
This type of pump is very common on combination pump and pressure tank units used for domestic wells.
They will often pick-up and fill an empty suction line but not always.
For use with a well, a foot valve is used to keep the suction line full.
Been there done that and have set up many of these pumps.
 

Part and Inventory Search

Sponsor