Uh no...
1806.1 says to use the values in the table if you are designing with ASD
You can increase the values in the table by a third if you are designing with LFRD
It is not related Qall vs Qult
I agree with msquared48 and BigH that, from the context, this is a Qall number. I don't see...
Thank you
Chapt 29 now concerns Plumbing Fixtures. All of the Soils and Foundations stuff is in Chapter 18.
Based on your response my feeling is that presumptive loads refer to allowable (not ultimate) loading.
This is what I needed to know.
Thanks again
I need some guidance..
Section 1806 of the 2009 IBC addresses presumptive load bearing values (displayed in Table 1806.2).
Does anyone know if these Qult or Qall values? Anyone have a source for this info?
Thanks