Thanks for taking the time to reply. Yes, its a standard design and it requires a big excavation! Variations on this design are used at different voltage levels.
If I'm understanding this correctly, treat each pole as having an independent fixed base foundation and design this to resist one...
Hello there
I need a push in the right direction to allow me to look at the foundation of a power line H pole assembly. The structure is an intermediate structure and as such is mostly subject to a lateral wind load acting on the conductors and poles. I've attached a drawing for reference.
I...
Thanks very much for your replies. The design is a standard one in my country. It was done approx 25 years ago for a certain maximum conductor size but the source calculations seem to have disappeared during industry privatisation etc! People are starting to talk about using larger conductors...
Hi there,
As you can see from my handle I'm an electrical engineer by training. However I'm trying to understand a power line terminal crossarm and I'm wondering how to approach it.
I've attached a drawing for reference. The crossarm consists of two back to back angles connected at the...