Hey, thanks for the quick feedback...
What I can take out from these comments is that:
A single standby generator HAS to be run in isochronous mode when isolated from the grid.
If an inverter cannot be run in droop mode, trying to run both in parallel would create a real mess in system...
Hi all,
Not sure where to post this...
I have some trouble understanding equipment protection on a grid-tied PV system, specifically when there's a backup generator behind a transfer switch supplying the same load.
UL1741 specifies that the inverter should disconnect if it senses...