Thanks guys, this question is due to an Aph-ground fault at the gen disconnect. The high voltage cables were not terminated at the same height, so the voltage gradient from the 7kV termination kit was less than an inch from the ground point (shield) of the adjacent Aph cable. An external...
My question is.... Post generator fault, 10MVA unit, what tests would you run before putting it back into service? Consider a) internal fault such as stator ground b) external fault such as a slow clearing bus fault.
I have mainly transmission experience and am not sure what all to consider...