Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. bozzah

    Calculation method for Substation bus structure due to short circuit currents

    Hello, I would like to learn the basis of calculation principles when it comes to design of substation bus structures. In particular, when it comes to the forces (kN) applies to the steel structure, equipment, cables with the respect to forces due to short circuit currents. Structural engineer...
  2. bozzah

    Inrush for transformers connected in parallel

    Hello, I'd like to know the method of calculating a combiner inrush current for transformer connected in parallel. In my case there are ten (10) 10kVA transformers connected in parallel, i.e. one 600V circuit (125A breaker) is feeding all 10 transformers (separation between transformers is...
  3. bozzah

    Controlling power factor for solar grid tie-in inverters

    I am trying to understand how to control power factor for grid tie-in inverters for ground mounted solar system (10MW). The solar site consists of ten 1MW inverter stations (2x500kW inverers). The AC output of the inverter is 480V at which point it transforms to intermediate voltage 27.6kV...
  4. bozzah

    Solar plant - transformer configuration

    The site is 8MW and it consists of 4 clusters (each cluster is 2MW package (2MW transformer and 4-500kW inverters)). Transformer secondary side is 480V (inverter input) and primary is 44kV. I am trying to see a benefit of transformer configuration (pri:Wye-grounded/sec:Wye). The other option...
  5. bozzah

    Transformer configuration and harmonics

    I am modelling a system with 5 medium voltage transformers feed to the common bus. On seconday side of each transformer are PV solar panels connected to DC/AC inverter. The inverter is connected to the secondary side of MV transformer. The inverter generates voltage harmonics (at the moment I...
  6. bozzah

    CT Saturation

    Scott, I had a similar concerns about CT excitation curve and knee point. Would you please explain/correct my understanding. Here the CT is C200, 1200:5A at 4.16kV. Let's say that total CT burden (including wire, relay, winding resistance) is 1 OHM. According explanation from one course I...
  7. bozzah

    Zero sequence current transformer - sizing

    So, in this application, the determining factor for the size of the CT is resistance grounded transfomer(25A) or this sizing is just a standard practice at this voltage? If transformer grounding resistor is, for example, 100A, an appropriate size would be say 200:5 for zero sequence CT?
  8. bozzah

    Zero sequence current transformer - sizing

    Referring to a single line diagram, I'd like to confirm the size of the Zero sequence current transfromer. Full load amps for this 4.16kV motor is about 800A. In addtion to 1600:5 CT(3), motor protection relay has a set of zero sequence CTs . Zero sequence current transforer (a set with single...
  9. bozzah

    Maglock vs. Electric strike

    A lot of good responses. thanks all!
  10. bozzah

    Maglock vs. Electric strike

    Rbulsara, yes, I am referring to magnetic door holders mounted close to the top of door. What about Electrical Code requirements with electric strikes? I guess it there is none, because for most of the egress doors one needs just to push the door to exit. There is nothing holding the door...
  11. bozzah

    Maglock vs. Electric strike

    Even though I understand the principles of operation, when do we use magnetic locks, i.e. electric strikes. Contractors generally run away from maglocks due to the facts there is more labour involved and they need to be interconnected with Fire Alarm pull station (if present at the door), so...
  12. bozzah

    electromagnetic door locks: theory of operation?

    the current when passed through a wire creates magnetic field arount the wire. When wire is wrapped around the iron core, magentic vector does not cancel but is parallel, hence the power of the field. maglocks operate on 12 to 24 V DC. They need constant source of current to remain locked. If...
  13. bozzah

    Detuned capacitor banks

    I am trying to get better understanding of detuned capacitor banks. I understand the basic prinicples with capacitor and inductors in series in order to avoid any harmonic that are present in the system. However, how the inductors are "tuned". There are tables with tuning frequencies, but no...
  14. bozzah

    45kVA transfromer controlled by a contactor

    After the conversations with a number of transformer manufacturers, there is no issue with switching it 2-3 times a day, which is the situation in my case. Having a switching contactor at secondary, would introduce additional cost since 45kVA (600V-208/120V)is a bit far from the source, 600V MCC.
  15. bozzah

    45kVA transfromer controlled by a contactor

    Are there any effects on a 45kVA transformer if the primary is switched on-off few times throughout a day? In order to siplify wiring, owner wants to control lighting panel by turing on-off the whole lighting panel via contactor on MCC; i.e. having primary side of the transformer is swiched...
  16. bozzah

    VFD and short circuit

    I'd like to know how does a VFD affect a short circuit level; two 7500hp motors (fed from 4.16kV, s/gear) are controled by VFDs. In case of the 3ph bolted fault at the gear, motors act as generators adding fault current at the bus. Having VFDs in series with motors, is there any change in fault...

Part and Inventory Search