  1. Runsor

    Transformer MV earth fault.

    Uneven CT saturation might be the reason. Taka a disturbance recording of the three phase currents when the motor is started and calculate the residual current.
  2. Runsor

    CT accuracy

    An old handbook states that a 5P CT at rated current and rated burden has less error than 1 % and 1 one degree. For a 10P CT the amplitude error is less than 3 % and angle error is not specified. I guess these are IEC specs. In practice the errors are smaller at least if the ratio is big and the...
  3. Runsor

    Arc around the commutator

    Thanks a lot. Tack så mycket.
  4. Runsor

    Arc around the commutator

    I would like to know the english term used about an arc burning in an electric motor around the commutator. "Circular arc fault at commutator" or how do you call this phenomena?
  5. Runsor

    Generator protection : Loss Of Field

    Here's an example of a rotor winding failure i.e. a total loss of excitation. This is from a real fault of an 18 MVA generator. Just the P, Q and f were recorded with 50 samples per second. There is no change in the active power at the moment the field diappears...
  6. Runsor

    ASEA minimum-oil circuit breaker HLR 123/2500

    A colleague of mine is looking after a service manual for an old ASEA minimum-oil circuit breaker HLR 123/2500. Any information is appreciated.
  7. Runsor

    Old Stromberg(ABB) motor protection relay

    Slavag, thank you very much for the manual.
  8. Runsor

    Old Stromberg(ABB) motor protection relay

    I'm trying to understand settings from an old SPAJ 3R5 motor protection relay by Stromberg (nowadays ABB). Where could I get a manual of this old relay? Google gives a hit on an ABB page, but it doesn't work. From the unclear old setting sheet from the customer I read that CT is 800/5 and the...
  9. Runsor

    GENERATOR EXCITATION SYSTEM

    Question: If there is a short circuit fault inside the generator or a fault between the generator terminals and the circuit breaker, does it help to immediately switch off the excitation with the CB trip signal? Or is it enough just to start the shutdown procedure after some delay?
  10. Runsor

    Moving a larger transformer on a railroad track

    I found the same recursive pictures from CargoLaw http://www.cargolaw.com/2005nightmare_catch-day.html#the-feature and the last picture appears to be a FAKE.
  11. Runsor

    Moving a larger transformer on a railroad track

    Here's a miserable recursive rescue operation http://shouthill.googlepages.com/files File: HoistingHoisters.pps
  12. Runsor

    Motor thermal overload protection, ANSI 49 with Sepam Relays

    The IEC 60255-8 thermal model is a simple single time constant model. The two time constants are by no means for hot and cold but for "running" and "stopped" situations. For generators and cables there may not be any difference between the heating and the cooling time constants. When the motor...
  13. Runsor

    Help finding typical inductance of large transformer

    The secondary inductance will be more near 10 H than 1 mH. If the name plate contains S0, the idle apparent power, that can be used to calculate the winding inductances. Anyway, I think dpc hit the nail on the head in his second comment:
  14. Runsor

    Harmonic filter

    Having three 700 uF capacitors in a Y-connection gives 350 uF for the line-to-line capacitance. There are two 700 uF capacitors in series: 700/2 = 350.
  15. Runsor

    L-G fault in 3-ph system

    AMBMI said that with a non-zero fault resistance in an isolated network you get something less than 1.732 Un = sqrt(3) Un for the healthy phase-to-earth voltages. Yes, that is mostly true, but the relation of Uo and fault resistance is actually quite complex. In fact with certain earth fault...
  16. Runsor

    Residual voltage and earth current protections coordination

    Vuan, you wrote "The MV system is neutral insulated, and only distribution transformers and reactive compensators are connected there." Does this mean that your network is compensated i.e. it is grounded with a Petersen Coil? If yes, do you have any resistor parallel with the Waldemar's coil...
  17. Runsor

    Funny nameplate

    Petronila mentioned mixing up 50 Hz and 60 Hz. 460 x 50/60 = 380, which is equal to 220 x sqrt(3). Is that a coincidence?
  18. Runsor

    Vector jump

    Here's a link to an IEEE article "A practical method for assessing the effectiveness of vector surge relays for distributed generation applications" http://www.multi.fi/~saunaaho/Files/VectorSurgeRelayEffectiveness.pdf But I think - and your case implies the same - that theory won't help...
  19. Runsor

    Vector jump

    You requirement for "correct settings" for ROCOF and vector jump is quite tough, because of the nature of these two protection criteria. Here's a link to a recommendation for ROCOF and vector jump settings for distributed generation by John E Nielsen, ELTRA. Table 2.8.2 on page 32 states the...
  20. Runsor

    Parallel Cable Load Imbalance

    gepman I agree with your interpretation of figure 5 of http://www.edadesignline.com/showArticle.jhtml?articleID=192200580 Please note, that this busbar geometry has nothing to do with the original question about two parallel cables. This link is just the first example of proximity effect on...