  1. KVX10

    Padmount transformer protection

    I don't mean to throw this thread off, but reading this brings up another question about protecting padmount xfrmrs. When protecting transformers and primary feeds to them, there are some that leave the bayonet fuse to protect the transformer and feeder fusing to protect the wire. I've seen...
  2. KVX10

    Lighting Question

    Here's the manufacturer that I am currently reviewing. http://www.fullspectrumsolutions.com/scart/public/database/repository/other/everlast_sheets/Parking-Series.pdf
  3. KVX10

    Lighting Question

    I'm not sure that this is the appropriate place, BUT here goes... I am about to review induction lighting fixtures versus using HPS fixtures for roadway lighting. There are a lot of pros for using them: high CRI, longevity, etc., however, I am hesitant on making a decision as far as...
  4. KVX10

    Sub Freezing temps and motor startup

    I've recently experienced electric motor startup problems like high thermal temps. for motors 150hp and larger that drive well pumps. I've never had to look into the realm of sub-freezing temps creating a larger current draw on startups as I live in a milder region of the country. I would...
  5. KVX10

    MV and HV Cable suppliers

    As mentioned before Okonite has sub cable available... http://www.okonite.com/Product_Catalog/section2/section2-pdfs/2-30.pdf
  6. KVX10

    Distribution Transformer Loading

    I was thinking in the same manner as WAROSS, but appreciate the other information you all presented. DPC, sometimes I assume too much when asking for opinions, thanks for your input. I am usually conservative when sizing transformers as I believe many are oversized, therefore inefficient...
  7. KVX10

    Distribution Transformer Loading

    I have run across Anthony Pansini's text and it gives recommended loading for distribution transformers. I believe that some of the recommended kVA ratings seem high. (Just my opinion) For example loading a 167kVA padmount transformer for up to 370kVA load under Table 6-13. I understand that...
  8. KVX10

    Disturbance Analyzers

    You may want to visit Power Monitors at www.powermonitors.com. Their rep visited our office showing their latest and greatest. I was interested in their products, but we are currently using Meggar products that are relatively new.
  9. KVX10

    Transformer Economics

    Can anyone refer me to a basic Total Ownership Cost (TOC) evaluation method for transformer purchasing for utilities? I am reviewing our method and it does not seem appropriate. Thanks!
  10. KVX10

    gas water heaters and electric meter clearance

    I have a contractor that wants to mount a instantaneous gas water heater 15" away from an electric meterbase. Our requirement mentions a gas "meter" to be 3' away from the meterbase, but does not mention gas appliances. I am looking for a standard that mentions a clearance for gas appliances...
  11. KVX10

    power cable pulling calcs

    1. In regards to pulling tension calcs, I am trying to determine the jam ratio pulling 4 cables through 6" conduit. Cables used are: 3-750kcmil diameter:1.73 per cable 1-4/0kcmil diameter:.98 per cable I am using the following formula: Ratio= 3D/n1d1+n2d2 Where D=inner diameter of conduit...
  12. KVX10

    Shunt Capacitor Placement

    Just another idea... Do you have a SCADA system with a load management option? If so, you can use the already installed SCADA system using load management switches that control oil switches to open or close in the capacitors.
  13. KVX10

    3-phase fault

    Thanks Bill and jghrist, Bill's explanation is along the lines of what I believed what is going on...with extra detail! Thank you for your comments. Could be awhile before a decent load will be picked up as the housing market is pretty bad.
  14. KVX10

    3-phase fault

    I'd appreciate it for some feedback/explanation of the following occurance... Presently there is a 3 phase 4 wire Y feeding a new subdivision at the end of the line with phase "a" and "c". On the way to the subdivision, there is a pump station with a 120/208 service that is radial fed. Before...
  15. KVX10

    Fusing

    The fuse would be on a "dip pole" radial feeding padmounts. Coordination is what is most important in most cases as jghrist responded. Thanks for the input.
  16. KVX10

    Fusing

    I am in a debate concerning fusing for a distribution system as far as wire and padmount transformers are concerned. There are two schools of thought here. One says to fuse to protect the wire and rely on the bayonet fuses within the padmount transformer, the other says to fuse to protect...
  17. KVX10

    Voltage Tool For Medium Voltage Insulated Underground Cable

    Try this site....we use this model. Voltage Detector - VDA040P (0 - 40KV) http://www.whsalisbury.com/safetyline/products/detectors.html
  18. KVX10

    Blinking Lights - Pole Top Cap Bank set 1 span from Line Regulators

    We experienced similar events as johnnyball. The frustrating thing was that we didn't suspect the regulator as it was only 2 years old. We operated the tapchanger manually and came across our problem. (If you are on site with the regulator you will probably hear it as well as see it on you...
  19. KVX10

    Transformers

    I was looking at a table that lists full load ratings for 3-phase transformer banks and ran across a 30kva, 3-phase, 120V listing. . . started talking about it with others and the debate is whether or not the only way to attain this 3-phase voltage is by a delta bank or by some other...
  20. KVX10

    Transformers

    Question: Is there any other way a transformer can provide 120V three-phase power besides a 120V-delta?