Thanks to all that have contributed to this thread. It has given me insight to several areas that I had not considered before, and as such, I guess I can say the thread has been a success to me personally.
I will proceed with solid grounding of the generator neutrals. The winding pitch, being...
Gordonl - Given that each of the generator breakers will already have a dedicated generator relay (incorporating a 50/51G), would routing the "summed" ct circuit through all three generator relays be reasonable? The burdens on todays microprocessor based relays will not be a problem...
I have read the thread "Multiple Resistor Grounding" and have gleaned good facts. Big difference here is solid grounding. Perhaps after discussion, solid grounding will be ultimately the thing to go...
The power generation is islanded, consisting of three identical 2/3 pitch...