I think you have several code issues besides NEC -500.
1) The gas water heaters need ventilation and combustion air (NFPA 54)
2) You indicate that the TX is 13KV and therefore needs to be in an 3-hr fire rated room (NEC-110.31(A).
3) NEC-500.5(B)(1)(3) indicates that locations where breakdown or...
Thanks ccjersey, powerwagon75, and waross for yor help.
ROI might be short for LEROI we do not know.
The Gen-set is located in a high-rise building in Miami, used for standby emergency power.
The engine is Natural Gas powered, with spark-plugs, and turbo charged.
We posted the question at...
I found an ROI Generator about 30 years old with following model #
Engine: ROI "Crown Line" H884-V8
Generator: Model# HAA4CU
Size: 5-3/8x4x7/8 or 5-3/8x4x7/85
Serial# 65X2348
Spec G-27790 - 1800 RPM
Can anybody help me to find the KVA or KW rating or guide me to...