I would not try this as it may well be a conflict of interest. Since you work fro Company A, you should address this with their Code of Business Conduct and Ethics committee. If they give a thumbs up, you ae covered...otherwise no.
Ken
Ken
KE5DFR
Add the 15 or 20 % over design tot he calculated heat exchanger surface. Then go back and recalculate the heat transfer cofficient based on the new surface area.
The fouling overdesign is taken care of in the fouling factor as opposed to clean tubes.
Ken
Ken
KE5DFR
This is pretty common practice for water coils in the HVAC industry.
If a customer insist, tey can generally be drovided with a dielectric flange set.
Ken
Ken
KE5DFR
Plan to put in Heresite coat coils or equal.
Remember that the A/C load is in tow parts, the sensible load and the latent load. The A/C will dehumidify.
Ken
Ken
KE5DFR
The refrigeration flanges are a unique design to the refrigeration industry. They are designed to provide a higher clamping force than the standard ANSI flanges.
I do not know how old your equipment is, but the trend has been to get totally away from flanges as much as possible and go with...
How long have the machines been operating?
What type oil is being used and is it suitable for low temp applications?
Have you aded any oil to the compressors?
Ken
Ken
KE5DFR
In addition to the "turbines" you will need adequate eve vents to allow air to move through the attic. You want to rid the attic of heat and humidity.
The approach to attic ventilation varies abit with regard to your location. Do you have cold winters or hot summers to deal with?
Ken
Ken...
As an engineer that has spent a lot of time in the field troubleshooting, I can say the experience you get from field work can not be valued. As a result of the field experience is love to get to do some trouble shooting, get my hands dirt and work with the technicians.
If you are willing to...
The vane position and capacity or power are not direclty proportional to each other. The control action will be much like you described.
Ken
Ken
KE5DFR
To scrub H2S out of the air you will need to look into some sort of a scrubber using a checmical process and possibly carbon beds. It won't be cheap.
Ken
Ken
KE5DFR
There is not a right answer that fits every case. You need to review the operating cost, longivity of equipment, how it is operated, installation cost, first cost, maintenance cost and available space to install.
Ken
KE5DFR
One of the most confusing things to "outsiders" in this industry is the rating of cooling towers and evaporative condensers, it even confuses a lot of the so called engineers as well. I wish that the manufactures would do away with the TON rating system and strictly rate them in total heat of...
Who in the world would use an NPT connection on a R-134a unit?
Since they are already there, you need to clean them well and coat them with A Loctite product specifically for refrigerant service. It will hold pretty well and can be heated to remove the plug later.
Ken
Ken
KE5DFR
It is not hard to use a simple dose tank to feed on the suction side of the pump. Pipe it up so that it can be isolated, and then pressurized with the pump discharge and push it in to the suction. You can pump or gravity fill the tank depending on the size.
Just some pipe and valves.
If you...