Dear SELEC,
From my knowledge with my national utility company, when we asked for fault values, they will give the MINIMUM fault (say 4000 MVA and translated into kA @ 132 kV) and MAXIMUM fault (say 5600 MVA) values.
The maximum is what the utility has predicted now and some future forecast...
Dear sykimk, please go to ABB website for Is Limiter articles. See below.
My Cogen project is located in Malaysia within a refinery and we have designed our 33 kV system with Is Limiter between our Cogen to Grid system - mainly to limit additional short circuit currents which otherwise would...
Dear all,
Thank you all for the replies.
Yes, of course, I have to make sure EITHER one of the gas insulated double-bus switchgear to be in DEAD condition, protections are disabled accordingly.
Yes, I believe there are two different compartments for each main and reserve bus.
I really hope...
Dear rraghunath,
Hi, I'm new here.
Regarding the double busbar system, you mentioned it's a rarity these days. I think Utility company still considered a double-bus system don't u think?
Anyway, just to check from all people's experience, how do you do BUSBAR EXTENSION work for the double-bus...