  1. HighPotter

    using a megohmmeter to test new, 15 kv shiled cable?

    On new installations of cable, our utility still requires a DC hi pot "proof" test, to what ever voltage the chart says. Our primary cable is EPR. This engineer wanted us to " meg " the cable, using a our Biddle 15kv meggar. I disagreed. I was looking for opinions on why he might want the...
  2. HighPotter

    using a megohmmeter to test new, 15 kv shiled cable?

    Thats my point, wareagle. I was told by an engineer to Megg a new installation of cable. I just dont understand what he was looking for from this sort of test. I have always DC highpotted a new cable installation, to most of the time, ATLEAST twice the rating of the cable. HP
  3. HighPotter

    using a megohmmeter to test new, 15 kv shiled cable?

    The word is " shielded"..I am sorry. Long day. HP
  4. HighPotter

    using a megohmmeter to test new, 15 kv shiled cable?

    What REALLY would this prove? This is shieled, jacketed 15kv cable, 3 conductors per conduit. The "run" is approx. 1000' long, with pole top terminations at each end. HP
  5. HighPotter

    15 kV J-box

    What type? What size? What sort of material? Ya got to give us something. HP
  6. HighPotter

    Connecting to tubular copper bus

    And it is square, hollow, copper tubular bus.
  7. HighPotter

    Connecting to tubular copper bus

    thanks everyone. Wow, Waross, those links are great. I'll check them all out. I can't see how just soldering this bus would be sufficient. But since you say the solder is actually stronger then the copper, I guess Im wrong. I am partial to a bolt together system, if rated properly...
  8. HighPotter

    Connecting to tubular copper bus

    We have some 3000amp rated, tubular copper bus work. Any suggestion on a good way to cut out a ssection, then put it back in? A splice you might say, between tubular, 3"square x 1/4" thick copper bus. Can copper bus be "welded" ? If so, what would be the best way? Or should "splice plates" be...
  9. HighPotter

    Utility Short Circuit Data Proprietary?

    Well first off, which utility? I have experience with most of them. HP
  10. HighPotter

    DC voltage dip

    When the batteries are only 3 years old, and its your ONLY bank, then strap and spG reading are the extent of testing. HP
  11. HighPotter

    DC voltage dip

    The AC dip was for slightly more then 50 cycles. The DC dip was only for 10 cycles. The bank was just recently tested and all was good. It was not however discharge tested or load tested. Have any of you heard of the term " Coup De Fouet " HP
  12. HighPotter

    DC voltage dip

    We have a bank of lead acid batteries providing substation dc power. Recently, during an event, we had a dip in our station power, which of course caused a dip on the input voltage to the charger. At the exact same time the station power dipped, our DC voltage dipped from 134v to 78v, but for...
  13. HighPotter

    available fault current

    Thank you Ron, I will check those out. HP
  14. HighPotter

    available fault current

    I am being asked to calculate, then mark(identify) 4 different locations, on a customers electrical infrastructure. Very simple installation. Small 3 phase service provided by the power company, then feeding several loads thruout the companies property. Is there software/info available where...
  15. HighPotter

    Phase Rotation Meter

    Thanks for your responses. In this case, the Troubleman marked the rotation prior to deenergizing the service, and then a different meter was used when checking before renergizing. Next time, the same meter will be used, regardless. HP
  16. HighPotter

    Phase Rotation Meter

    Is this possible? CustomersElectrical service is to be replaced. One type of rotation meter is used to mark rotation on the 480v 3 phase service. Phasing is marked " blue-white-red " Clockwise rotation After customer service is replaced, the service is energized to the meter and checked with...
  17. HighPotter

    high carbon dioxide levels

    moisture content -- 7ppm interfacial tension-- 47.9 Electricpete, How long would the sample have to be subjected to sunlight? Hours? days? Our bottles are clear as well as our glass syringes. thanks for everyones opinions hp
  18. HighPotter

    high carbon dioxide levels

    To all that have chimed in, thanks for your thoughts. I learn so much at this site. I do not have the data with me at home, but here are some answers off the top of my head. The transformer is NOT a GSU The transformer is sealed nitrogen The transformer is approx. 24 years old The...
  19. HighPotter

    high carbon dioxide levels

    Here is an example of the latest testing for the transformer in question (15mva 66/7kv) hydrogen: 0 methane: 45 ethane: 17 ethylene: 2 acetylene: 0 carbon monoxide: 728 carbon dioxide: 28900 And here are the results from 6 months ago... hydrogen: 0 methane: 55 ethane: 23 ethylene: 4...
  20. HighPotter

    high carbon dioxide levels

    We have several transformers that come back from lab testing with high carbon dioxide levels. ( over 10,000 ) Now, we have a small wager on this.... Can the "manner" in which you take the oil sample, substantialy effect the outcome of the test regarding carbon dioxide? HP