Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. Gene1203

    Tin plated lugs to silver plated busbar

    Would tin-plated lugs connected to silver plated busbar cause problems? I need to connect 500MCM copper wires to the bus with crimping lugs (UL Listed 540H). The copper busbars are silver plated. Your inputs are appreciated.
  2. Gene1203

    Why 1.8 meters (6 feet) is the maximum length of flexible conduit?

    Thanks for the tip wareagle. The edition of NEC I have is 2002 and 348.60 is about grounding and bonding. So it has all to do with grounding - flexible conduits are not recognized as a ground path. Can I get a yes or no to my previous question then?
  3. Gene1203

    Why 1.8 meters (6 feet) is the maximum length of flexible conduit?

    Thanks very much Contrivers & wareagle. To summarize your replies and tips, the code does not limit the length of any flexible conduit as long as there is a separate grounding conductor run inside it and the conduit run is properly supported as required by code. Is this correct?
  4. Gene1203

    Why 1.8 meters (6 feet) is the maximum length of flexible conduit?

    Is there an electrical engineering calculation why the code does not allow more than 1.8m or 6 ft of flexible conduit in installations such as taps for lighting fixtures or motor terminations?
  5. Gene1203

    Generator Voltage Dip

    Sett: The unit in question is running as single unit - not synchronized with the other units. There are 3 units one of which is new where the problem occurs. Synchronizing is used when transferring the load from one unit to another. jbartos: I agree with you. Actually, the operators are...
  6. Gene1203

    Generator Voltage Dip

    RAMconsult and e5fornow: Thank you very much for the insights. I will follow your advice. Will let you know the results. I really appreciate it.
  7. Gene1203

    Generator Voltage Dip

    The generator is brushless.
  8. Gene1203

    Generator Voltage Dip

    Our client reported that they are experiencing an unpredictable and irregular voltage dip with their power supply. They have their own power plant using diesel engine generators. On a particular single-unit operation, they reported that the dip occurs once a month, after two months and twice a...
  9. Gene1203

    Minimum Generator Loading

    alehman: Thank you very much. I think we have the same point of view. Can I e-mail you directly? I would like to ask you some items I am afraid I cannot post here. Also, I do not have any info as to who to contact directly for the manufacturer of the generator in question. I feel you can...
  10. Gene1203

    Minimum Generator Loading

    Yes, there are 3 units (2 old and one new). That is why we need to provide the user a recommendation that in the event that the load (when they are using the new unit), falls below 30-35% (but the supplier insists 50%) of the new unit's capacity, they have to operate one of the old units and and...
  11. Gene1203

    Minimum Generator Loading

    rbulsara and alehman: The load as I have mentioned reaches to more than 80% of the generator capacity - this depends on the demand of course. The minimum load usually occurs at night time - but not always. At daytime, the minimum load is around 50%. The generator was sized to handle the entire...
  12. Gene1203

    Minimum Generator Loading

    rbulsara Thanks so much for the quick reply. Actually, we have a project where we supplied and installed a prime rated generator. What we observed is it slobbers (wet stacking) when the load falls below 40% of its rated output. This was observed by the supplier themselves. Now, the supplier of...
  13. Gene1203

    Minimum Generator Loading

    I am looking for some standards and/or publications regarding the recommended minimum load (%) of generators (diesel engine-driven) with respect to their rated output - particularly on prime duty generators. I appreciate the help. Thanks.
  14. Gene1203

    Mounting Height of EXIT Lights

    Hello. Can anybody help me regarding the mounting height requirement of EXIT lights as per NFPA? I am currently engaged in an on-going construction of a laboratory building and most of the exit lights are located in corridors with three (3) meters ceiling height measured from the finished floor...
  15. Gene1203

    Is Lightning AC or DC?

    For the attention of jbartos: Correct me if I'm wrong but do I perceive your Jul. 2 post as: AC can be modelled out of a "string" of lightnings - (just) for the purpose of showing an AC wave? You personally don't mean to say that lightning itself maybe alternating to the effect that...
  16. Gene1203

    kVA vs. Watts

    Theoretically, AC systems whatever the load maybe, shall have a power factor due to the line and load impedance that is a function of the frequency. That is why VA (volt-amperes) was introduced. The watts is for DC systems. However, for minimal loading and in the absence of any motor loads, as...
  17. Gene1203

    Harmonics

    Tonymag, Try this: http://www.mikeholt.com/studies/harmonic.htm Also, this is a very practical and interesting one: http://www.haworth.com/pdfs/e2636.pdf
  18. Gene1203

    Is Lightning AC or DC?

    I'm with jbartos here. I also have the book "Standard Handbook for Electrical Engineers" 13th Edition by Donald G. Fink and H. Wayne Beaty. I went to these pages and the illustrations shows clearly the charges. It is discussed here (in the handbook) that lightning stroke is...
  19. Gene1203

    Help on SC Calculation: Second xfmr downstream with motor loads

    I think we have gone too far here. Thanks to all of you for the TIPS. We have different point of views obviously. What I was hoping to get from these posts is a common thinking of what was initially asked: whether the motors downstream of a second transformer may be considered for the...
  20. Gene1203

    Help on SC Calculation: Second xfmr downstream with motor loads

    To rhatcher and jbartos, a big THANKS. For rhatcher: I would not like to consume much of your time but here goes: "- the conductor size and # of parallel conductors for the 480V feeder to the transformer" 5 sets of 3-250mm sq. THW in cable galv. steel cable ladder "- same...

Part and Inventory Search