  1. Tumppi

    Need Quick Braking of Induction Motor

    The setting of Unidrive SP you need to change is parameter 2.04 which is ramp mode selection. At default it is Std = standard ramp and it will longer deceleration time if dc-link voltage is rising up to trip level. Set pr.2.04 to Fast = fast ramp and you will decelarate according set ramp rates...
  2. Tumppi

    Drive for Line Shaft

    The reason for oscillation is slip compensation of open loop drive. Your motor slip is 60rpm and syncronous speed at 50Hz is 1500rpm. When you set motor nominal speed to 1500, then slip compensation is off. Normally slip compensation for open loop drive works with the load/current. What higher...
  3. Tumppi

    How to Control AC 600V PM motor???

    Few facts about PM motors aka brushless ac motors: It has Permanent Magnet rotor with very strong magnets. You can not run PM motor with vector drive, even if you have feedback encoder on the motor. You need encoder/feedback device that can give absolut position of rotor for commutation, when...
  4. Tumppi

    Omron VFD Problem

    There are two things you should know,when selecting braking resistor.The minimum ohmic value for the drive and the power rating for the braking resistor. Minimum ohmic value can be found from manufacturers manuals. (What lower is resistance,that higher is current). Power rating can be...
  5. Tumppi

    VFD and Light Curtains

    About EN954-1. Control Techniques UNIDRIVE SP got this feature as standard. (NO options needed).It is caled SECURE DISABLE-function and it meets the requirements of EN954-1 : category 1, 2, and 3 for machine safety.