Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations cowski on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. rempman

    Pole Mounted Transformer

    First of all study the nameplate. Is this a single phase unit or three phase? If single phase the previous answer is likely correct. And there are ways to either extend the connecting paddles or add more. If it is three phase look to see if there is a mid-winding tap for a third voltage...
  2. rempman

    Delta on a Wye system

    The biggest issue may be if you are feeding the transformer with any length of Underground Cable. We had such a ferroresonance issue that we now spec all of our pad-mounted transformers with LBOR switches. If that is not possible use a three phase device to protect the primary cable system...
  3. rempman

    Are skirts of termination kits on the same phase allowed to touch?

    As has been brought up previously by allowing the skirts to touch is not the recommended practice. We avoid this by installing a piece of 4in copper bus drilled to NEMA hole pattern. In an overhead application we also include a bail off one side to hang an arrestor, thereby eliminating any...
  4. rempman

    Ungrounded power TR in grounded network

    In the design of the transformer and substation was there a fault current study done? Where do you want the zero sequence currents to go. Typically protection engineers like to see the zero sequence currents return to the source transformers of the system, not to through the load transformers...
  5. rempman

    Ice & Wind Maps for 2007 Edition of the NESC - ANSI C2

    For those concerned with Ice and Wind loading on conductors and structures as it relates to applying the National Electrical Safety Code (NESC) please refer to the 2005 edition of ASCE 7 that has just been published. The 2007 edition of the NESC will include this map.
  6. rempman

    240v 3-phase with Open Delta Transformer

    When looking at the ability to calculate the fault currents and capacity of the bank you need to keep the following in mind: 1) You are typically dealing with transformers of vastly different sizes. Something like 50 kVA and 15 kVA or any other combination. As a result when doing per unit...
  7. rempman

    underground aluminum conductors

    As you know in the underground utiltiy systems there are generally two classes of systems: URD - 200 Amps or less and the 600 Amp systems. These are classified by the ratings fo the accessories that are available such as terminations and splices. If there is a chance that moisture may get into...
  8. rempman

    Guidelines on Load Diversity

    If you can get access to Pacific Gas & Electric's design manual there is a great section on diversity of loads. Puget Sound Energy also has a good discusion on the subject.
  9. rempman

    reflected wave

    I see that we have had a wonderful discussion on theory and transmission lines. The simplist method of limiting the amplitude of reflected wave is the installation of arrestors on the end of terminal lines. This would apply to both transmission and distribution. I might suggest that the...
  10. rempman

    Unbalanced Voltages of Open-Wye Open-Delta Banks

    The bank you describe is usually provided for small commercial facilities that typically have single phase load in addition to a limited amount of three phase load. If you look at the bank I would guess that one transformer is quiet a bit larger than the other. Something like a 50 kVA (likely...
  11. rempman

    Electrician's fish tape activator?

    There is fishtape on the market that has a tracer wire included. The idea being you could put a tone on it and trace it with a reciever. Try FiberTek Tracer tape: http://www.fibertekinc.com/pull_details.cfm?ID=5
  12. rempman

    Closing switches

    Even though you did not state it specifically I must assume you are referring to Transmission Class switches (55kV and above). We have what I might call 3-1/2 versions of transmission line switches on our system. Arcing horns (for droping line charging current), Vacuum bottle switches (for...
  13. rempman

    Transformer Loading Guideline?

    Your question is a good one. My response makes the assumption that your firm falls under the ANSI C2 - NESC instead of NFPA 70 - NEC. In distribution utility applications within a residential setting you can plan to overload transformers up to 200% or more of nameplate. This is depending of...
  14. rempman

    Corona Ring

    A couple of years ago I had to research and create a specification for bidding 230kV NCI's. A good reference is: Outdoor Insulators Authors: Ravi Gorur, Edward A. Cherney, & Jeffery T. Burnham Copywrite 1999 by Ravi S. Gorur, Inc., Phoenix, Arizona 85044, USA Specific to corona rings you...
  15. rempman

    Sizing personal protective grounds on a 15kV distribution system

    When it comes to Personal Protective grounds you are treading on a sensitive area. Refer to ANSI Standard F855 for sizing of conductor and clamps. You will need to know what your available fault current is in order to size the components properly along with a good idea as to how quickly your...
  16. rempman

    My house has intermitant power brow

    Any of the possible sources you mention may be a problem. Any "shorts" that would cause a draw on voltage to a point of effecting other devices will likely be at a higher temperature than it should be at the point of the "short". If you can not find a source inside your...

Part and Inventory Search