Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations cowski on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. mmt019

    Locating Oil type transsformers inside building

    NOt sure what you mean by "globally". I would be in an industrial setting in an electrical room in USA.
  2. mmt019

    Locating Oil type transsformers inside building

    Is there a problem with locating a 7.5 MVA oil transformer inside a building? I would use FR3 oil and still build a containment area for it.
  3. mmt019

    Is cable properly protected or not?

    I need some opinion. Attached is the image of the one line which shows a 3750 kVA transformer (XFMR-MSC-1). As it is a supervised location so as per NEC table 450.3(A), the transformer secondary protection is not required if the rating of transformer primary fuse is maximum 250%. However the...
  4. mmt019

    De-rating Required for Cables for Frequencies other than 60 Hz According to NEC

    Is there anything in the NEC about de-rating cables due to frequencies other than 60 Hz. I am working with 100 Hz.
  5. mmt019

    Replacement rheostat for synchronous motors

    I have six M-G sets from the 1940's where the synchronous motor utilizes a motor operated rheostat. The field voltage is 250VDC. The rheostats are in old and in need of replacement (or repair). I have not been able to locate a manufacturer for rheostats. I have tried Ohmite, Cutler-Hammer...
  6. mmt019

    Synchronous Machines

    Does anyone happen to know of the best reference for theory on synchronous machines and the theory behind the various field exciter equipment options for these machines? There is alot of reference material out there on the subject but is there one that is preferred among the EEs out there?
  7. mmt019

    NETA MTS-2011 Microhm Contact Resistance Measurement

    NETA MTS-2011, Part 7.6.1.1, Section 3.2.3 indicates that the contact resistance, in this case on a molded case circuit breaker, that in absence of manufacturer's data, the standard suggests to investigate the problem if a value deviates from adjacent poles or similar breakers by more than 50%...
  8. mmt019

    Megger test results

    The readings appear to be acceptable in accordance with NETA ATS-2009. I'll reiterate what others are saying: Check with the manufacturer, verify that the 'B' phase arrestor is the same as the others, retest.
  9. mmt019

    Odd Phase to Ground Readings on Delta Transformer

    Just a follow up to my problem, the ground fault was found to be a tubular heater (strip heater) for a synchronous motor and it was connected on 'B' and 'C' phase. Thanks for your posts!
  10. mmt019

    power system protection video

    Give this website a shot. I took a course in person with the instructor and he is very knowledgeable with this subject. Copy and paste on the link below. http://www.brainfiller.com/stores/productlist.aspx?CatId=7 Good luck!!
  11. mmt019

    Odd Phase to Ground Readings on Delta Transformer

    Our electricians record monthly readings and for years, it typically has read normal, 277V. So a change of some sort has taken place. A classic ground fault reading should have caused the faulted phase to drop to a much lower voltage. In this case, 'c' phase increased significantly.
  12. mmt019

    Odd Phase to Ground Readings on Delta Transformer

    I have a switchgear lineup that is fed by a 6MVA 6900/480V oil transformer, Delta configuration on both sides. On the switchgear, I am getting unexplainable V(line-ground) readings as follows: Va-g=215V, Vb-g=225V, and Vc-g=390V. Normal readings would be Vline-grd=277V. Phase to Phase...
  13. mmt019

    14 % Harmonic Distortion at residential customer

    Sounds like your best option is to move or become an Amish farmer. On a more serious note, turn off all of your feeder circuits on your panelboard and then see what your getting. This may clue you in to where the problem may be occurring. If your THD problem disappears with all your feeder...
  14. mmt019

    5A CT secondary

    What is the manufacturer and Cat # of the CT?
  15. mmt019

    How to determine winding material?

    I'm with rhatcher on this one. I work at an Air Force Base with 1940's-1960's transformers and I have never seen aluminum windings on a transformer. They built transformers like tanks back in the 40's-60's. This is a "utility grade" transformer Reasons why I think it is copper: 1. Size is...
  16. mmt019

    acceptable values for Bus Ductor Test

    Zogzog pretty much has it correct EXCEPT NETA says to investigate values which deviate from those of similar bolted connections by more than 50% of the lowest value. Typically, the similar connections are the different phases and you are comparing the readings on A, B, and C phases. Readings...
  17. mmt019

    Emergency Diesel generator

    I am assuming "idle" means that the generating is not running but is available to be started for backup power. For general emergency backup electrical power purposes, once a week "no load" generator exercising for 1/2 hour is acceptable with at least once a year 100% load testing (for 3-4...
  18. mmt019

    how far from water (sinks) do panels need to be?

    Clarification: Strike out "in any direction". Also the 3.5 ft. is measured from the front of the panel.
  19. mmt019

    how far from water (sinks) do panels need to be?

    NEC Table 110.26.(A).(1) condition 2 says 3.5 ft. minimum in any direction. You might want to consider it in a wet location, so Section 312.2.(A) should be taken into consideration. You may want to consider a NEMA 4 enclosure which is protection against splashing water or hose directed water.

Part and Inventory Search