Thanks Brad. The suggestions are very helpful. Do you think there will be any issues if I go with the screws to about 39 mm effective embed ( 51 mm of nominal embed) 24 mm clear cover on the other side of panel?
Hi KootK.
Thanks for the insights of what might go wrong. In this I am specifically out of anchors to fasten to 3" concrete skins as none of the wedge anchors or HAS threaded rods work for 3" concrete ( HILTI tables for minimum embedment and concrete thicknesses). So there are no strength guides...
Hi All.
I am a early structural EIT trying to design post Installed anchors on to 75 mm thick RC concrete wall panels.
The minimum thickness of the concrete member needs to be effective depth of anchor +30 mm cover which does not work. ( Hilti tables). The triangular structure made out of angles...