Tek-Tips is the largest IT community on the Internet today!

Members share and learn making Tek-Tips Forums the best source of peer-reviewed technical information on the Internet!

  • Congratulations TugboatEng on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. lvsenthil

    VFD alternatives

    Dear Bruce, It's obvious the current (power) will increase when you arrest the bleeding in a positive displacement blower. Instead you should reduce the flow by reducing the speed. Apart from VFD you may reduce the speed of blower by changing the Drive pulleys . It is cost effective one.
  2. lvsenthil

    3.3 KV MOTOR OVER CURRENT PROTECTION SETTING VALUES?

    Dear afzumannu (Electrical) Based on your input, Considering the the Motor Rated current 28 A, Rated Voltage 3300V, 160KW, CT 40/1 You may set the following I > 1.2x 28/40 0.84 Pick up time for I> 10Sec I >> 6x 28/40 4.2 Pick up time for I>> 0.05 sec Disable I>>> your back...

Part and Inventory Search

Back
Top