What refernce are you using for fittings equivalent lenght?
Also do I consider each valves when calculating the total head?
Pipe lenght, fittings, coil press drop, valves (?) --- are this the information i need when do pump head?
Thank you in advance.
Cooling Cap = density x water flow rate x delta T
Or
(Short cut) BTU/hr = 500 x GPM x dT
30% propylene, EAT: 10 LAT: 98.2 EWT: 170 LWT: 150
What will be the density value to get the GPM?
Thank you in advance.
Anybody can guide me where can I find the equivalent fitting loss for duct and pipe using ASHRAE handbook? I'm browsing my online access of ASHRAE handbook but can't find the tables for equivalent lenght.
Also, when we do the total static pressure head I use % for getting the fitting pressure...