Good Afternoon,
I need help in determining whether the CT we have meets the fault requirements.
The CT is a 1000:5 5P20 30VA Protection CT - I have a saturation curve with a knee point at 140V. Rct (Secondary Winding res.) = 0.245 @75C
The max fault I need to design for is 32 kA.
I understand...