I have 3 phase 480/208-120 delta/zig-zag transformer that gave me bad ratio when tested with a Vanguard TTR test set. Any ideas how to ratio this transformer using a voltage source on the primary and a voltmeter on the secondary?
I have two identical 3 phase dry type transformers I am trying to parallel:
1.5 MVA 15kv/480v Z=7.2% Dy11
They are being fed from the same source. I measured voltage across A-A B-B and C-C before closing the tie breaker and they measured 47 V. Voltages between phases are all the same, 480v. Is...