Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: azadani
  • Content: Threads
  • Order by date
  1. azadani

    CB spec. for filters in SVC

    I would like to have some feedbacks on CB,s used in SVC,s in steel companies. we had a CB failure(explosion) in a 2nd harmonic filter.(33 KV CB).we are recommended to use 72.5 kv CB,s for all 2nd ,3th ,4th and 5th harmonic filters.The questions are:1-Are CB,s rated 50 HZ suitable for switching...
  2. azadani

    SVC - CB spec.

    I would like to have some feedbacks on CB,s used in SVC,s in steel companies. we had a CB failure(explosion) in a 2nd harmonic filter.(33 KV CB).we are recommended to use 72.5 kv CB,s for all 2nd ,3th ,4th and 5th harmonic filters. The questions are: 1-Are CB,s rated 50 HZ suitable for switching...
  3. azadani

    Ground grid design-limiting touch voltage

    we are invoved in designing ground grid for a 63/20 Kv sub.(area: 120*80 sqm).The fence can not be included within ground grid area.the outer ground wire is 1 m inside the fence. our reccomendation is to isolate the fence from the grid and earth it seperatly but our client wants to connect the...
  4. azadani

    SHORT LINE PROTECTION WITH DISTANCE RELAY

    Hi. Although relay manufactuerers claim their distance relays are capable of protecting short lines ( less than 10 Km) effectively provided SIR is less than 30 . It is also claimed that CVT transients have no major effect on the operation of relay. Meanwhile most of electric design engineers and...
  5. azadani

    Mv VT primary fuse burnt out

    dear freinds. There are some VT primary fuse burnt outs in the newly energized 24 Kv metal clad switchgear.there is no short circuit in vt secondary side.it mostly happens in the time of swiching of 132/20 KV transformers.Two 20 KV outgoing feeders supply 20KV overhead lines. vt,s have 1/4 of...

Part and Inventory Search