If Ksd = Ksq = 1/S100
Then as far as I understand, you can assume...
Xdv = Ksd * (Xdi - Xl) + Xl
and
Xqv = Ksq * (Xqi - Xl) + Xl
Can this be applied to the transient and sub-transient reactances as well?
Thank you
Is there an equation to relate saturated and usaturated values for a synchronous generator.
I have the S(1.0) and S(1.2) values with saturated T'do, T"do,T'qo,T"qo,Xd,Xq and unsaturated X'd,X'q,X"d=X"q, and Xl. Is there any way to calculate the missing fields?
....Saturated/Unsaturated...
I am trying to calculate the Inertia constant of a generator for testing purposes using collected data. I also have software that will model transient stability studies. When I provide the model with the following information:
H=2
MW = 50
MVA = 156.25
I recieve the following data, simulating...