Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: Mike6061
  • Content: Threads
  • Order by date
  1. Mike6061

    Earth Resistance

    A colleague and I were having an argument regarding earth resistance. He argued that between any (2) earth electrodes the resistance of the earth resistance would be (depending on the soil)1000s of OHMs. I disagree. I argued that most of the resistance would occur around the areas immediately...
  2. Mike6061

    Paralleling MV Generators

    We have MV generators that distribute at 4160V.For plant operations the generators are connected to a common bus. Up to (4) feeders originate from this common bus through SF6 switches that provide overcurrent protection. The generators have a nuetral tap that can be bonded to ground but...

Part and Inventory Search