Fuel Control Workroom Ventilation Building:
We have a writeup is readdressing the issue that they question the adequacy of the ventilation system in this explosion proof room. We have never before had reason to believe it was not functioning as designed, but when the IG visited he smelled JP8...
I have (3) 21' x 7' x 6' Sump
Dear Friends,
We are being told to prevent this sump water from freezing. I don't know how to spec a heater that would be enough to keep this sump water around 40F when ambient temperatures fall below 40F. I think it will have a thermostat to control the heating...
I have (3) 21' x 7' x 6' Sump
We are being told to prevent this sump water from freezing. I don't know how to spec a heater that would be enough to keep this sump water around 40F when ambient temperatures fall below 40F. I think it will have a thermostat to control the heating operation. This...
I am a new HVAC Engineer. My boss assigned me to work on a new Fire Station HVAC Load calculation. I used Elite Software CHVAC and Trane Load Express to calculate, I came up with very low BTU/hr for heating load and he said on the RULE of THUMB (can anyone explain this on Cooling & Heating) that...
Can experience technical personnels who are experience with Co Ray Vac products please share your current or past experience of Co Ray Vac products (Infrared Heating). I am about to make a major purchase on this product to heat our aircraft hangars. They are coming out with a new product that...
Dear Friends,
What resources to look at the minimum depth to prevent underground pipe from freezing (chilled water services with PVC). I am in Enid, Oklahoma. Thank you very much!!!
I just got a warning letter from Oklahoma City about erosion problem from our new church construction site. We need to fix it ASAP before getting a fine. These are things we need to finish this weekend.
Possible solutions:
1) Laying about 5000 sft of sod to prevent erosion problem.
2) Cleaning...
I am using Load Express (Trane), Load Express asks for Loss Coefficient (Btu/hr.F.ft) while Elite software (CHVAC) asks for Floor Slab Coefficient. Are they the same meaning? Can anyone explain to me what are the different between them. Thank you very much!!!
I have 54'dia. x 35 crt chilled water storage tanks for thermal storage. Our tank contractor provide a submittals for cathodic protection and since I don't have any technical knowledge on cathodic protection, could anyone please point me to the right direction for cathodic protection specs...
I am trying to figure out the maximum daily output for our 12" sewage piping to our wastewater basin. In order to calculate the maximum flow rate, what data do we need to include in our formula or what formula to use?
Thank you in advance for your help and contribution!
I am trying to figure out the maximum daily output for our 12" sewage piping to our wastewater basin. In order to calculate the maximum flow rate, what data do we need to include in our formula or what formula to use?
Thank you in advance for your help and contribution!
I am going to purchase an AJAX boiler which is 30% more capacity than then RITE boiler because the AJAX salesman told me they do not have the 1,050,000 btuh so we have to purchase the 1,500,000 btuh. What effect will we have to use an oversize Natural Gas boiler. Please help ASAP!!!
Do you agree with this statement:
"The 4” drain/fill nozzle is for both functions, as its name indicates. "
Can we use 1 nozzle for both drain/fill functions for our thermal storage tanks or do we have to use 1 nozzle for drain and 1 nozzle for make-up water?
Thank you so much!
What do we use to connect PVC & Steel pipes? Pipe expansion required? Would that effect the insulation? Can the transition be within the concrete (thrust block) from outside to inside the building? This application is for Chilled Water Supply and Return.
Thank you
My drawing indicates the Honeywell 3-way modulating Control Valves on the Supply side (modulating the return side), shouldn't the Valve be on the Return Side for Chiller Water and Hot Water System? I thought it was a drawing error. Would that effect the flow efficiency if it's located on the...
Our shop determination for BX brand would be Rite, but some wants to use Ajax. Any of you have any suggestions?
-----------------------------------------------------------
Hot Water Boiler Schedule:
165 GPM
Input: 1,050,000 btu/hr
Output: 872,000 btu/hr
Fuel: N/Gas
Remark: Natural draft venting...
Dear friends,
I don't know if anyone of you ever utilize the Lochinvar Copper-Fin II Gas Boiler before? We are replacing this one with existing steam boiler. Our shop never have experience with this type before.
Btu/hr input = 1,260,000
Btu/hr output = 1,058,400 (84% efficiency)
CSD-1 Code...
Tank contractor propose to use Tnemec for protective coating, anyone use this product before?
1. Surface Preparation:
a. All interior and exterior weld preparation, grinding, removal of weld flux and splatter to be performed prior to Abrasive blast cleaning
b. Interior surfaces...
Tank contractor propose to use Tnemec for protective coating, anyone use this product before?
1. Surface Preparation:
a. All interior and exterior weld preparation, grinding, removal of weld flux and splatter to be performed prior to Abrasive blast cleaning
b. Interior surfaces...