Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: EP007
  • Content: Threads
  • Order by date
  1. EP007

    80% vs 100% LV Circuit Breaker

    The circuit breaker is 800 A frame and 80% rated, which is 640 A, The adjustable rating plug, can be easily set to say 500 A. The trip unit, which is separate, can be set as a multiple of 500 A. Can the breaker carry 500 A as that is less than 640 A, or does it now become limited to 400 A?
  2. EP007

    Medium Voltage Contactor Dropout Time

    Medium voltage (4.16 kV system) vacuum contactor dropout time is important for fuse-contactor coordination. Some vendors have values between 15-25 ms, and others, several cycles, which I have been more used to seeing in the past. Compare that to a 3 or 5 cycle vacuum breaker, and 15-25 ms is...
  3. EP007

    Steel Tube as Ground Electrode

    I have multiple foundation steel piles to be used as grounding electrodes. They each appear as a hollow cylindrical steel tube or pipe, perhaps 5/8 inch thickness, and could be driven 10-13m to solid rock. O.D is not selected, but perhaps 8-12 inch. Has anyone seen a methodology to represent...
  4. EP007

    LV CB Open time with electronic trip for arc flash

    For a LV molded case circuit breaker, equipped with electronic trip unit, the tripping curves may only include the trip unit time, but may not include the CB opening time thereafter. Has anyone seen manufacturer's data on this? The application is arc flash analysis.
  5. EP007

    VSC Harmonic Model

    I have a VSC, voltage source converter, connected to the power system. The VSC is a PWM inverter. The power supply system fixes the voltage, say 460 V, as well as the frequency 60 Hz. For harmonic studies on the power system, my view is that the VSC should be modeled as a harmonic voltage...
  6. EP007

    VFD Model for Harmonic Analysis

    For harmonic analysis on industrial power systems, I normally see the VFD's represented by current harmonics, for ac induction motor applications, and pulses of 6,12,18, etc. Now I see a report that represented the VFD's by voltage harmonics. The software is not an issue as it can accept both...
  7. EP007

    Mysterious Harmonic Impedance (scan)

    To characterize their system, the power company provides a frequency scan, which is the equivalent impedance at each frequency, output from their software (CYMDIST). At each frequency they give a number (magnitude) for each of the phases A,B,C, all different. I see three apparent issues with...
  8. EP007

    Structure Deflection

    I am trying to have an appreciation of the numbers I see for single wood pole (tangent) deflections, however, it is not my field. Poles should deflect in strong winds. I also notice that some are leaning without wind, which must be due to foundation, or perhaps pole age. The maximum deflection...
  9. EP007

    Motor Differential Protection

    Our team is discussing the need for motor differential protection on a 3000 HP motor, 4.16 kV. There is high resistance grounding, 10 A, which is important since a stator ground fault, is low current, and can be cleared quickly by the MPR (motor protection relay), without any time advantage of...
  10. EP007

    Arc Flash - Extent of Study

    I'm wondering how far all the experts are presently taking the arc flash analysis to. I have a 480 V MCC which supplies loads such as VFD's, motors, unit heaters. I've been on sites where tests were made at each of these, with covers off. The hazard could therefore exist, which implies analysis...
  11. EP007

    Cable Insulation Hi-Resistance Ground

    The 4.16 KV system has an NGR, 5A continuous. For a ground fault in the zone of service transfomer secondary and 4.16 KV SWGR main breaker, that breaker will open. The transformer primary has only a fuse, which will not open for the small current. The fault will then persist and be alarmed, but...
  12. EP007

    CB Opening time

    For the 5 cycle breaker, I see in IEEE 242 a 0.20 sec CTI, coordination time interval between static relays. I also see arc flash calculations using 0.083 (5 cycle) for the same equipment. Shouldn't these numbers be the same?

Part and Inventory Search