If I have a 120v circuit with 10A and one with 16A which totals 26A. But when I calculate for required total BTU/hr for cooling CFM, it doesn't come out to what my conditions currently are.
But since both of the circuits have a common Nuetral, would the total amps for these 2 circuits be...
I have a room that is supplied by 60 F air at 570 CFM and it is maintaning 74.5 F. With no people or lights on in the room.
If I calculate the Sensible Heat at CFM * 1.08 * Delta T or 570*1.08*14.5= 8926 BTU/Hr
Now if I want to convert this to watts to determine the room load. I divide the...