Hi
I am trying to find a source for de-gas and reclaim transformer oil.
I need what initial values induce oil processing and what are the acceptable values after de-gas and reclaiming.
The IEEE 637 is too old, I tried SDMyers –ask Charley
Thanks
We have a Zigzag transformer that had Bucholtz trip probably due problems on external line.
Immediately the customer takes DGA from bottom. The Hydrogen was 14 PPM and other gases also low. No C2H2, C2H4, 5 PPM.
Because this low values the transformer return to service and had another trip. Than...