  1. ougrad1999

    Transformer Powering Reading

    we powered up a 12.47kv/4.16kv, three phase, delta-wye XFMR and the follwing readings were taken: A to B 4160 A to C 4160 B to C 4160 A to A 5kV B to B 2.5KV C to C 2.5KV A to Gnd 2.4kV B to Gnd 2.4kV C to Gnd 2.4kV what seem to be the problem? we've the doble and TTR testing before...