We have recently adopted PCC-1 torque figures for bolting B16.5 flanges.
Feedback from the technicians is that the gaskets are now being found with the spiral windings crushed into the pipe bore and the outer rings are tending to cup.
We use Flexitallic spiral wound gaskets with 'flexicarb'...