Is anyone very familiar with this pump. We are having trouble getting the correct parts for it. The distributor has sent us the wrong mechanical seals. Now they sent us a sleeve, which is not what we need. The stationary seal is also wrong.
In my previous thread I asked about heat balance and efficiency testing. Since i will have to talk about this next week with the auditor, I have a basic question. What would cause such an imbalance in evaporator tonnage to condenser tonnage. The tubes have been cleaned recently. The machine was...
Has anyone done a chiller efficiency test. We are getting some weird numbers. Heat balance is supposed to be 5% or less. We are getting 30% to 40%. The machines are running well, tubes have been cleaned. They are carrier low pressure 540 ton. These are my readings I took at this moment:
ref...
Our expansion tank (glycol system for comfort cooling) runs at a positive pressure when the system is off and goes into a vaccuum when running, sometimes as much as 20 Hg. Is this normal.Seems like a pretty high vaccuum.
System: Three 540 ton chillers, two 260 ton chillers. supplying 6 main...
Our CHW pumps are housed in boxes stuffed with insulation. The insulation stays wet from sweating and it's starting to rust the piping. Has anyone found a better way.