Transformer is rated 3500kVA 25kV/480Volts Delta-Delta.
Ungrounded delta secondary is causing variable speed drive problems.
Please recommend best means to ground this transformer.
Transformer: 3750kVA
Primary: 12.47kV Wye solidly grounded(connected to the utility line).
Secondary: 2400V Delta
Experiencing occasional 51N trips, that is, primary neutral current. 51N relay picks up at 2.0A.
51N current all the time about 1.0A; with 300:5A CTs equates to 60A primary.
One time...