Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: nya1
  • Content: Threads
  • Order by date
  1. nya1

    Wild leg power

    I have encountered problems with a 5 HP 230/3/60 volt pump service. The motor is a 230/460 (dual wound) motor. The problem does not ocur when using real 3 phase power. The amp draw is normal and balanced. FLA is 14.7A, max reading is 12.8A On a wild leg service the pump draws almost 25%...

Part and Inventory Search