Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations cowski on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: recs
  • Content: Threads
  • Order by date
  1. recs

    GF Protection on LV 3-Wire Unbalanced Systems

    If a 3-phase, 3-Wire (no Phase to neutral loads), Y-G, 480V system has several phase-to-phase loads unbalancing the system. I would like to provide GF protection at the service disconnect and a second level at the feeder. All 600 A frame breakers I have seen (Eaton, GE, and Square D) have GF...
  2. recs

    Short-Circuit Withstand Rating for Motors

    According to NEMA MG 1-2011 section 32.13, generators can withstand a maximum short-circuit current equal to the three phase fault current at its terminals for at least 30 seconds (unless otherwise specified by the manufacturer) when operated at rated kVA and power factor and with a maximum of...
  3. recs

    CT SIZING FOR PRIMARY PROTECTION RELAY

    Lets assume that we have a 10,000 kVA 138 kV to 12.47 kV transformer with a primary FLA of 41.8 A. The short-circuit available at the secondary side of the transformer is 5.76 kA which referred to the primary side is 520 A. Assuming this CT feeds a typical electromechanical 50/51 relay (CO...
  4. recs

    Electric (not electronic) circuit simulation

    Does anybody knows of a software that can draw and calculate steady state single phase electrical circuits? I have SKM but is not what I want. SKM is an excellent program but it can't draw the single phase schematic diagrams, including phase, neutral, and equipment grounding conductors and then...
  5. recs

    Standard Sizes for MV or HV Circuit Breakers

    The NEC allows for transformer protection to go to the next standard size. It is very clear how to apply this rule for low voltage circuit breakers. But what are defined the medium voltage or high voltage breaker standard sizes?
  6. recs

    Contradiction is Scope for Part 32 in NEMA MG 1-2011

    In standard MEMA MG 1-2011 Section IV Part 32 the title shows the following: "Synchronous Generators (Exclusive of Generators Cover By ANSI Standards C50.12, C50.13, C50.14, and C50.15 Above 5000 kVARatings". Then in the scope section establishes that this part 32 covers synchronous generators...
  7. recs

    IEEE Std. C37.102-2006 Voltage Restrained Relay for Short, Short-Circuit Time Constant

    In IEEE Std. C37.102-2006 related with generator protection, it is recommended to use voltage-restrained back-up protection when the following condition is present (Section 4.6.1.2 Overcurrent Type Backup, page 77): Short, short-circuit time constant. The actual wording is: "On units that have...
  8. recs

    Comparison of UL 1066 and ANSI C37.13

    UL 1066 and ANSI C37.13 are recognize standards for Low Voltage Power Circuit Breakers (LVPCB). Are these standards equivalent, in other works, did ANSI or UL adopted one of these standards from the other organization? If different, what are the main differences? Thanks.
  9. recs

    Which short-circuit current to use when checking coordination time intervals (CTI)

    When performing a coordination study on a MV system, we can use many types of short-circuit currents in the TCC curves. If we use the ANSI C37 standard for calculation, we have many types of short-circuits to show in the TCC. Some of these are: 1. Momentary: Calculated using the first-cycle...
  10. recs

    Intermediate Zone Characteristics of Cables- Error in IEEE Std. 242 2001?

    IEEE Std. 242 2001 in page 314 describe how to obtain the overload curves (i.e. intermediate zone characteristics) for cables. this is the zone between the continues load capability and the short-circuit capability. It says: "Intermediate zone characteristics of medium-voltage cables and 75...
  11. recs

    Transformer Impedance and Full Load kVA

    I understand that the transformer nameplate impedance (Z%) is related to the nominal kVA. I also understand that this impedance will change if we consider the full-load kVA of the transformer. The result is that the short-circuit current delivered by the transformer is the same no matter which...
  12. recs

    %Z When Using Full Load kVA

    I know (as a rule of thumb) that the %Z of a transformer with multiple kVA ratings changes according to the kVA rating. For example if a transformer has a 2,000 kVA Nominal rating and a 2.500 Full Load kVA rating and the published %Z is 5.5% (at Nominal kVA rating) the %Z at Full Load kVA...
  13. recs

    Polarity Marks on CT's

    Does anybody know a detailed guide for polarization marks in current transformer relays? I understand how the polarization marks work when the primary CT current ENTERS the primary CT and the polarization mark of the primary CT is at the entrance (begining of the coil. But I do not uderstand...
  14. recs

    Motor Damage Curve

    I am doing a coordination study and want to protect a medium voltage motor with a relay. To do this I need to know the damage curve of the motor. If I would know this curve I can plot it. Where can I obtain standard motor damage curves for different types of motors? Thanks. RECS

Part and Inventory Search