Hi,
I have an application where we have of small number of "essential" motors (~10 motors, total load 15kVA) from a total load of 1200kVA.
As the load is so small I would prefer not to use a diesel back up generator. I was thinking of specifying a solid state UPS to support the load.
I was...
Hi,
Does anyone have any useful links to technical and reference data on Rotary UPS?
Any experiences/insights anyone may have would be most welcome
Regards
Sean
Consider a packaged substation as follows:
Two 2.0MVA 10kV - 0.4kV Dyn11 vacuum cast resin transformers TA and TB (close bus coupled to the switchboard).
Two main incomer ACBs to off-load the transformers T9A and T9B
Low voltage switchgear section split into two buses Bus A (normally fed by TA)...