IEEE C62.22 recommends that for a delta connected primary you configure 3 arrestors in a wye configuration (rated at line to neutral voltage) with a fourth arrestor connecting these three to ground. Ref IEEE C62.22 Figure Eight on Page 28 (Sect 5.5.4.2).
Does anyone have any physical drawings...
IEEE C57.12 includes single phase to ground, two phase to ground and three phase faults as withstand tests/design criteria for liquid filled transformers.
Is it logical to assume that a transformer should withstand a three phase TO GROUND thru fault on the secondary as well. This is sometimes...