Hi
we recently repaired a 66 kV oil filled cable which was damaged by third party
Upon doing the final I/R test, the blue phase to earth reading was 92 M ohms. R and W phases were both in the range of 2.5 G ohms. the phase to phase readings were as follows R-W 3 G ohms , R-B and W-B 440 M ohms...
hi
we recently used 3 - 3 core cables ( one cable for each phase - for ampacity issues ) for the lv of a 33/6.6 kV T/F and there was a resultant current circulating through the armour of the cable which was connected to the T/F lv cable box and the earth bar of the switch gear.
can anyone say...