Eng-Tips is the largest forum for Engineering Professionals on the Internet.

Members share and learn making Eng-Tips Forums the best source of engineering information on the Internet!

  • Congratulations JStephen on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: Rocky1991
  • Content: Threads
  • Order by date
  1. R

    SLG Fault Calculation at Bus3 (High Side Start Grounded - 33kV) for three winding Aux Transformer (Hand Calculation)

    Can someone please help with solving Single Line to Ground fault current at the Bus3 (33kV) of the below single line diagram, single line parameters are as below: Grid: 3Ph Fault current 50kA, X/R =14 1Ph Fault Current 50kA, X/R =14 TF1: 285/142.5/42.5 MVA, 330/33/33 kV, Yn0d1d1 Positive...

Part and Inventory Search

Back
Top