Hello
Hello
I have a load= 200 KVA PF=100% so Amps = 288.7 but in load flow analysis load=191 KVA and Amps = 280.2 before circuit breaker , and load=188 KVA and Amps=280.2 after circuit
breaker the length of cable = 10 m why this difference ?
thank you...