Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: ahhie
  • Content: Threads
  • Order by date
  1. ahhie

    SF6 purity requirement in 66kV switchgear

    hi, I am working on 66kV switchgear maintenance. I like to know what is the minimum requirement for the SF6 purity (% volume). I cannot find it on the manual, it only give dew point requirement like -5 degree C for switchgear and -10 degree C for circuit breaker. Thank you.
  2. ahhie

    MK 30 Automatic Voltage Regulator

    We have 3 66/11 kV system transformers (18.8/27MVA) connected in parallel. Each transformer 11kV side have tap changer to keep the voltage at 11kV. I am wondering why some of automatic voltage regulator (MK 30) failed (indicated on it display screen), hence no automatic voltage regulation if the...
  3. ahhie

    CDG Guru Needed.

    Hi, I have this relay at site which may be more than 15 years old. The relay type is CDG31EG2012JD5. This relay is 3 poles Standard Inverse curve from the number 31 but is it 1.3s/10x curve, 3s/10x curve or other? Thank you.
  4. ahhie

    Trip curve for Mitsubishi Electric NF800-S breaker and Merlin Gerin Se

    Hi, Anyone have trip curve for Mitsubishi Electric No-Fuse Breaker NFE 800-s and Merlin Gerin Selpact In=1600A with protection type DN2 characteristic? I have try on the internet but cannot find. I suppose it is very old type. Thank you.
  5. ahhie

    Moeller NZM12-1000 (ZM12) MCCB

    Hi, I have NZM12-1000 MCCB at site which I do not know much about. How to know the setting for overload time Tr is ON or OFF? This is a thermomagnetics type. Thank you.
  6. ahhie

    time/current characteristics

    Dear all, Where can I find the time/current characteristics for the 800A type J fuse used in Merlin Gerin LV SAIF feeder pillar (Type 1601). I have try the fuse manufacturer site - Lawson Fuses but did not find one. Hope someone can help me on this? Thank you.
  7. ahhie

    Voltage across VT secondary fuse holder

    Hi, A new 3 phase 110V VT circuit with earthed neutral, the cables and instruments connected to it have been meggered and found to be earth-free. Why 48V is measured when voltmeter is applied across the top and bottom of each of the three fuse holders? The three core cable is about 250m long. Is...

Part and Inventory Search