hello again,
I got insane heat transfer coefficients. Average velocity of 1.5m/s, gets Re 152 000 for liquid Ra134a.
With that I get C1 0.021 and m 0.84, C2 0.98, Pr 3.32
Cross flow about aligned pipe stack.
so C2*C1*Re^m*Pr^0.36 gets me about 50 000?
formulas from Fundamentals of Heat and mass...
Hello,
can I calculate heat transfer parallel to pipe axis with the same formulas as heat transfer along a flat plate? I was reading several articles and there is always just heat transfer perpendicular to pipe axis.
As the pipes are quite long, flow is turbulent, so I think, the HTC will be...