I'm trying to reflect a fault level through a single phase transformer winding. I know I can use the %Z and the rated current to get the maximum unlimited secondary fault current. But If I know the actual level on the primary, how do I relect it thru to the secondary? I cannot just use the...
I am missing something in the NEC. #220.3.B.9 states that for a 20A circuit they allow 13 receptacles. This is only if they allow the breaker to be loaded 100%. I thought I had to size the breaker to 125% of the load or limit the load to 80% of the breaker. By this method, the limit is 10...