Tek-Tips is the largest IT community on the Internet today!

Members share and learn making Tek-Tips Forums the best source of peer-reviewed technical information on the Internet!

  • Congratulations MintJulep on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: mssengr
  • Content: Threads
  • Order by date
  1. mssengr

    reason for low silica in boiler blow down even CBD is closed

    We are operating four boilers at 105 Kg/Cm2 pressure. Silica in their steam drums is as low as 120 ppb. CBD, IBD and sample coolers valves from their drums are also closed. Moisture in flue gases are also analyzed showing no tube leakages. we fail to understand why silica is so less? BFW being...

Part and Inventory Search

Back
Top