The bottom of the slab (footers) are set at 12" below grade in this project, The code in this area requires 6" (mid-Atlantic region). So I think I am covered for frost heave.
I like the way you rolled the stirrup into the upper grid, I may borrow that vs the dual hook setup I show in my...
R13
When I request the soil report for a 28 X 10 Foot area how many samples should I expect to be taken? I would expect sample need to be taken throughout the slab area of coverage.
Thanks in Advance
-Tim C.
Sent From My TI-84+
Hello Engineers
My background is in electrical engineering but I am helping to design an equipment slab (which will eventually be reviewed by a PE).
I have designed the slab using the PCA method and Back checked it with the GRDSLAB spreadsheet that is available online.
Does anyone have a set...
There is no dynamic loading, the slab is sized for the equipment only. No vehicle traffic on fork truck (or none of the sort).
The seismic aspect is not a concern here.
I will look into the wind loading aspect. The gear is surrounded by a facility on three sides, the gear is basically sitting...
Ahh, I see
I will look into this aspect.
When (in your experience) an equipment slab is set, is it common practice to get a soils report? Or if the soil is compacted to the 95% density on the proctor test is this sufficient to handle an equipment slab?
Thanks in Advacne
-Tim C.
Sent From...
I found this as I was researching Slab On Grade Calculations used as equipment slabs:
https://www.macallisterpowersystems.com/solutions/engineering-toolbox/generator-set-foundations/
Best Regards
-Tim C.
Sent From My TI-84+
I understand that my numbers are based on total chiller skid weight vs the actually linear weight per foot of a single chiller.
My reasoning for this was that it would make the pad more than thick enough, and second, if I went with a single chiller liner weight per/FT, the pad thickness would be...
Would someone involved in daily RC Concrete design mind looking over an equipment slab I setup.
In summary, the pad is an equipment pad designed to accommodate (3) uniform wall loads of approx 450 LBS/FT.
The equipment is a chiller skid weighing approximately 17,000 LBS with the pad sized to...