Georgeverghese,
Both instruments work for total level (level of liquid hydrocarbon).
They are installed in a position that is expected to have condensed hydrocarbon. So they are not designed to measure the interface between liquid HC and Glicol+water.
The tubing line that you mentioned is the...
Hello Danw2,
I used the following data to calculate the head temperature error:
See attached the error calculation from Rosemount Instrument Toolkit.
Best Regards,
Pedro Henrique Sousa Prado...
Danw2, thank you very much for your attention.
The graph unit is percentage.
The difference betwen the transmitters vary from 5% to 10% (most in 8% - 80mm in level as we have 1000mm between process connections).
In the graph, the yellow trend is the percentage difference betweem them.
As our...
Dear,
I am having problems with level measurement in a vessel.
In this vessel, we have 2 level transmitters (one for safety and one for control) and both are DP transmitter with diaphragm seal.
Those transmitters are connected in different process connection, being them:
- Control Level...