Thank you all for your answers.
The transformer was installed before I was hired, they've just never calculated the impact on the equipments. There are many similar cases (20 transformers + 100+ branch breakers) covered in the analysis so I won't list every impedance but it should be around...
Hi all,
I've recently done a short-circuit analysis on EasyPower to evaluate the impact of replacing a 1.5 MVA xformer by a 2 MVA. What came out is that the old FPE 50H breakers cant withstand the new Icc of over 50kA (about 55kA) so I am considering two options:
1. Replace every breaker by an...